10A.20.010 Size of Water Meters.
This section is included in your selections.
The Director shall establish the size of water meter required to serve a premises in accordance with the American Water Works Association standards. The following safe operating capacities shall be the maximum capacities permitted for the corresponding meter size.
Meter Size |
Maximum Intermittent |
Maximum Continuous |
---|---|---|
3/4 inch |
30 Gallons/Minute |
15 GPM |
1 inch |
50 Gallons/Minute |
25 GPM |
1 1/2 inch |
100 Gallons/Minute |
50 GPM |
2 inch |
160 Gallons/Minute |
80 GPM |
3 inch |
300 Gallons/Minute |
------ |
4 inch Turbine |
1250 Gallons/Minute |
1,000 GPM |
4 inch compound |
500 Gallons/Minute |
------ |
6 inch Turbine |
2500 Gallons/Minute |
2,000 GPM |
6 inch compound |
1000 Gallons/Minute |
------ |
(Ord. 88-23 §20, 1988).